(a) This Act shall be known
as the "National Building Code of the Philippines" and shall
hereinafter
be referred to as the "Code".
SECTION 1.01.02: Declaration
of Policy
(a) It is hereby
declared
to be the policy of the State to safeguard life, health, property, and
public welfare, consistent with the principles of environmental
management
and control; and to this end, make it the purpose of this Code to
provide
for all buildings and structured, a framework of minimum standards and
requirements by guiding, regulating, and controlling their location,
siting,
design, quality of materials, construction, use, occupancy, and
maintenance,
including their environment, utilities, fixtures, equipment, and
mechanical
electrical, and other systems and installations.
SECTION 1.01.03: Scope
(a) The provisions of
this
Code shall apply to the design, location, siting, construction,
alteration,
repair, conversion, use, occupancy, maintenance, moving, and demolition
of, and addition to, public and private buildings and structures.
(b) Additions,
alterations,
repairs, and changes of use or occupancy in all buildings and
structures
shall comply with requirements for new buildings and structures except
as otherwise herein provided. Only such portion or portions of the
existing
building or structure which have to be altered to effect the addition,
alteration, or repair shall be made to conform to the requirements for
new buildings or structures. Alterations should preserve the aesthetic
value of the building to be altered.
(c) Where, in any
specific
case, different section of this Code specify different materials,
methods
of construction, or other requirements, the most restrictive shall
govern.
SECTION 1.01.04: Application
(a) This Code shall
apply
to all buildings and structures constructed and any change or repair
made
thereon after the approval of said Code. Buildings or structures
constructed
before the approval of this Code shall not be affected thereby; Except,
where their continued use or occupancy is dangerous to life or limb; or
where alterations, additions, conversions, or repairs are to be made
thereon,
this Code shall apply only to such portions of the buildings or
structure
which have to be altered in order to effect such damages or repairs.
(b) This Code shall
apply
to chartered cities, poblaciones of municipalities and municipal
districts
with a population of at least two thousand (2,000) inhabitants, and to
barrios of urban areas with a population of at least two thousand
(2,000)
inhabitants. This Code shall also apply to any area where there are
fifty
(50) or more families per hectare.
(c) This Code shall
likewise
apply to any area proposed for or being developed into a new town site,
residential subdivision, commercial or residential site, school site,
housing
project, and similar construction projects where five or more buildings
not covered by paragraph (d) of this Section will be constructed even
if
the poblacion or barrio population is less than two thousand (2,000) or
the density of population is less than fifty (50) families per hectare.
(d) The design and
construction
requirements of this Code shall not apply to any traditional indigenous
family dwelling costing not more than five thousand pesos (P5,000.00)
and
intended for use and occupancy of the family of the owner only. The
traditional
type of family dwellings are those that are constructed of native
materials
such as bamboo, nipa, logs, or lumber, wherein the distance between
vertical
supports or suportales does not exceed 3.00 meters (10 feet); and if
masonry
walls or socalos are used, such shall not be more than 1.00 meter (3
feet,
3 inches) from the ground: Provided, however, That such traditional
indigenous
family dwelling will not constitute a danger to life or limb of its
occupants
or of the public; will not be fire hazard or an eyesore to the
community;
and does not contravene any fire zoning regulation of the city or
municipality
in which it is located.
chan robles virtual law library
(e) Notwithstanding
paragraph
(d) of this Section, this Code shall apply to Group A dwellings
produced
on a commercial scale and intended for use by the general public.
SECTION 1.01.05 Building
Use Affecting Public Health and Safety
(a) Any building or
structure,
or any ancillary or accessory facility thereto, and any alteration or
addition
to any building or structure already existing, shall conform in all
respects
to the principles of safe construction, shall be suited to the purpose
for which the building is designed, and shall, in no case contribute to
making the community in which it is located at eyesore, a slum, or a
blighted
area.
(b) Adequate
environmental
safeguards shall be observed in the design, construction, and use of
any
building or structure for the manufacture and production of any kind of
article or product which constitutes a hazard or nuisance affecting
public
health and safety, such as explosives, gas, noxious chemicals,
inflammable
compounds, or the like.
SECTION 1.01.06: Maintenance
(a) All buildings or
structures,
both existing and new, and all parts thereof shall be maintained in a
safe
and sanitary condition. All devices or safeguards, which are required
by
this Code in a building or structure when constructed, altered, or
repaired,
shall be maintained on good working order.
SECTION 1.01.07: Insanitary,
Unsafe, Hazardous, or Dangerous Sites
(a) The land or site
upon
which will be constructed any building or structure, or any ancillary
or
auxillary facility thereto, shall be sanitary , hygienic or safe. Where
the land or site is polluted, insanitary, unhygienic, unsafe, or
hazardous,
conditions contributing to or causing its being polluted, insanitary,
unhygienic,
unsafe, or hazardous shall be reasonably improved or corrected, or
proper
remedial measures shall be prescribed or incorporated in the design or
construction of the building or structure in accordance with the
provisions
of this Code.
(b) The land or site
upon
which be constructed a building of structure or any ancillary or
accessory
facility thereto, for use of human habitation or abode, shall be at a
safe
distance from streamers or bodies of water and/source of air considered
to be polluted, volcano or volcanic site, and building or structure
considered
to be a potential source of fire or explosion, such as ammunitions
factory
or dump and storage place for highly inflammable material.
SECTION 1.01.08: Dangerous
and Ruinous Buildings or Structures
(a) General. - The
provisions of this Code shall apply to all dangerous buildings, as
herein
defined, which are now in existence or which may hereafter be
constructed,
as well as to ruinous buildings as defined in Article 482 of the Civil
Code of the Philippines.
chan robles virtual law
library
(b) Dangerous
Buildings
Defined. - Dangerous buildings are those which are structurally
unsafe
or not provided with safe egrees, or which constitute a fire hazard, or
are otherwise dangerous to human life, or which in relation to existing
use constitute a hazard to safety or health or public welfare, by
reason
of inadequate maintenance, dilapidation, obsolescence, fire hazard, or
abandonment; or which otherwise contribute to the pollution of the site
or the community to an intolerable degree. Any building or structure
which
has any or all of the conditions or defects hereinafter described, or
conditions
or defects similar thereto, shall be deemed to be dangerous building:
Provided,
That such conditions or defect exists to the extent that the life,
health,
property, or safety of the public or its occupant are endangered:
(1) Whenever any door,
aisle,
passageway, stairway, or other means of exist is not of sufficient
width
or size, or is not so arranged as to provide safe and adequate means of
exit in case of fire or panic;
(2) Whenever the stress
in any materials member or portion thereof, due to all dead and live
loads
is more than one and one-half times the working stresses or stresses
allowed
in this Code for new building of similar structure, purpose, or
location:
Provided, That in determining working stress, the working stress
method of analysis shall be used, and in the case of engineering "overstress",
the ultimate strength method;
(3) Whenever any
portion
thereof has been damaged by fire, earthquake, wind, flood, or by any
other
cause, to such an extent that the structural strength or the stability
thereof is materially less than it was before such catastrophe and is
less
than the minimum requirements of this Code for new buildings of similar
structures, purpose, or location;
(4) Whenever any
portion
or member or appurtenance thereof is likely to fall, or to become
detached
or dislodged, or to collapse and thereby injure persons or damage
property;
(5) Whenever any
portion
or member or any appurtenance or ornamentation of the exterior thereof
is not of such sufficient strength or stability, or is not so anchored,
attached, or fastened - place so as to be capable of resisting a wind
pressure
of one-half of that specified in this Code for new buildings of similar
structure; purpose, or location without exceeding the working stresses
permitted for such buildings;
(6) Whenever any
portion
thereon has wracked, warped, buckled, or settled to such an extent that
walls or other structural portions have materially less resistance to
winds
or earthquake than is required in the case similar new construction;
(7) Whenever the
building
or structure, or any portion thereof, because of: (i) dilapidation,
deterioration,
or delay; (ii) faulty construction; (iii) the removal, movement, or
instability
of any portion of the ground necessary for the purpose of supporting
such
building; (iv) the deterioration, decay, or inadequacy of its
foundation;
or (v) any other cause, is likely to partially or completely collapse;
(8) Whenever, for any
reason,
the building or structure, or any portion thereof, is manifestly unsafe
for the purpose for which it is being used;
(9) Whenever the
exterior
walls or other vertica structural members list, lean, or buckle to such
an extent that the structure falls within the condition described in
the
preceding subparagraph (2), above, or whenever any portion thereof
suffers
a material reduction of the fire and weather resistance qualities of
characteristics
required by this Code for newly constructed buildings of like area,
height,
and occupancy in the same location;
(10) Whenever a
building
or structure, used or intended to be used for dwelling purposes,
because
of inadequate maintenance, dilapidation, decay, damage, faulty
construction
or arrangement, inadequate light, air, or sanitation facilities, or
otherwise,
is found to be unsanitary, unfit for human habitation, or in such a
condition
that is likely to cause sickness or disease;
chan robles virtual law
library
(11) Whenever any
building
or structure, because of obsolescence, dilapidated, condition,
deterioration,
damage, inadequate exists, lack of sufficient fire-resistive
construction,
or other cause, is found to be a fire hazard;
(12) Whenever any
portion
of a building or structure remains on a site after demolition or
destruction
of the building or structure is abandoned for a period in excess of six
months, so as to constitute a nuisance or hazard to the public;
(13) Whenever any
building
or structure is in such a condition as to constitute a public nuisance
defined in Article 694 and 695 of the Civil
Code of the Philippines.
(c) Abatement of
Dangerous
Buildings. In all cases of dangerous buildings, except those
covered
by Article 482 and 694 to 707 of the Civil
Code of the Philippines, the Building Official shall order their
repair,
vacation, or demolition in accordance with the following procedure:
(1) Where the dangerous
building can reasonably be repaired such that it will no longer be
dangerous,
it shall be ordered repaired;
(2) Where the dangerous
building is such that to repair it would cost more than 50 per cent of
the current to replacement cost of the building, it shall be repaired
or
demolished at the opinion of the owner;
(3) Where the dangerous
building poses an immediate threat to life, limb, or property, it shall
be vacated immediately, then repaired or demolished in accordance with
subparagraphs (1) or (2) herein.
SECTION 1.01.09. Alternate
or new Design, Material, Method of Construction, or Workmanship; Tests:
(a) Any design,
material,
method of construction, or workmanship not specifically included in
this
Code may be used: Provided, That such alternate or new design,
material,
method of construction, or workmanship is at least the equivalent of
those
prescribed in this Code in effectiveness.
(b) Tests for design,
materials,
method of construction, or workmanship shall be prescribed by the
Secretary
of Public Works and Communication in appropriate rules and regulations
therefor.
SECTION 1.01.10: Municipal
and Provincial Ordinances and Regulations
(a) Local ordinances
should
conform to the Code and suppletory requirements hereto shall in no case
diminish minimum requirements embodied in this Code. The Secretary of
Public
Works and Communications or, in the proper case, the Secretary of
Justice
shall take any and all appropriate steps in cases where local
ordinances
conflict with the Code.
SECTION 1.01.11: Definitions
and Tables
(a) The definitions in
Annex
A and the Tables in Annex B of this Code are hereby adopted as part
thereof.
SECTION 1.01.12: Separability
Clause
(a) If, for any reason,
any section or provision of this Code shall be declared
unconstitutional
or invalid, no other section or provision of this Code shall be
affected
thereby.
SECTION 1.01.13: Repealing
Clause
(a) Any and all
statutes,
orders, ordinances, rules and regulations or parts thereof,
inconsistent
with the provisions of this Code, are hereby repealed or modified
accordingly.
SECTION 1.01.14: Effectivity
(a) This Code shall
take
effect upon its approval within the Greater Manila Metropolitan Area
and
in other areas where there are already existing local building codes,
and
four (4) years thereafter, in all other areas in the Philippines:
Provided,
however, That this provision shall not prevent any city or municipal
council
or board from adopting this Code immediately upon its approval.
Chapter
1.02 -
ENFORCEMENT
SECTION 1.02.01: Joint
Building and Environmental Planning Research and Standards Commission
(a) Membership.
There
is hereby created a Joint Building and Environmental Planning Research
and Standards Commission composed of two Senators, two Congressmen, and
five other members to be appointed by the President of the Philippines.
The members shall elect a Chairman from among themselves.
(1) The President of the
Senate shall designate the chairman of the Committee on Housing, Urban
Development and Resettlement and one Senator from the minority party as
members of the Commission.
(2) The Speaker of the
House
of Representatives shall designate the Chairman of the Committee on
Housing
and one Congressman from the minority party as members of the
Commission.
(3) The President of
the
Philippines shall appoint two architects, two engineers, and one
building
contractor chosen from those officially recommended by their respective
national professional organizations, to serve for four years or until
their
successors shall have been duly appointed and qualified.
(4) The members thereof
shall serve without compensation: except, That the members from the
professional
organizations may receive a per diem of one hundred pesos (P100.00)
each
per meeting actually attended: Provided, That the total per diem the
members
may receive shall not exceed six hundred pesos (P600.00) per month. A
monthly
transportation allowance of two hundred fifty pesos (P250.00) shall be
granted each of the members from the professional organizations.
(b) Duties and
Responsibilities.
The Commission shall have the following duties and responsibilities:
(1) Conduct or cause to
be conducted continuing research and studies on building, housing, and
environmental planning standards and requirements to safeguard life or
limb, health, property, and public welfare;
(2) Prepare a draft of
a
uniform code of criteria, standards, and detailed specifications
covering
design, construction, and other related matters suited to local needs
and
indigenous conditions for adoption by local governments to supplement
the
minimum standards provided in this Code;
(3) Prepare drafts of
environmental
planning, management and control codes, subdivision policies and
standards,
zoning regulations and other codes for legislative enactment; and
recommend,
from time to time, changes in this Building Code for submission to
Congress;
and
(4) Transmit
appropriate
recommendation to the Secretary of Public Works and Communications as a
basis for the promulgation by the Secretary of the necessary rules and
regulations to carry out the provisions of this Code.
(c) Technical Staff.
The Commission shall be assisted by a Technical Staff which shall be
headed
by an Executive Director and an Assistant Executive Director. All
personnel
shall be appointed by the Chairman subject to civil service laws,
rules,
and regulations.
(d) Appropriations.
The
amount of two hundred and fifty thousand pesos (P250,000) or such
amount
thereof as may be necessary for the operation of the Commission is
hereby
authorized to be appropriated out of any funds not otherwise
appropriated
for the fiscal year ending June 30, 1973. Such sums may be necessary
for
the operating expenses of the Commission in succeeding fiscal years
shall
be included in the annual General Appropriations Act.
SECTION 1.02.02: Secretary
of Public Works and Communications and Building Officials
(a) The Secretary of
Public
Works and Communications, hereinafter referred to as the "Secretary",
shall
promulgate such rules and regulations necessary to enable the Building
Official to enforce the provisions of this Code.
(b) In municipalities,
the
Municipal Engineer shall be the Building Official; Provided, That when
there is no such Municipal Engineer, or a duly licensed engineer
performing
the duties of a Municipal Engineer, or a Land and Building Official,
the
Provincial Engineer, or in the absence thereof, the Public Works
Engineer
within whose jurisdiction the municipality falls shall be the Building
Official. In case of cities, the City Public Works Supervisor shall be
the Building Official: Provided, That when there is no such
City
Public Works Supervisor, the City Engineer shall be the Building
Official.
For the purpose of the enforcement of the provisions of this Code, the
Building Official shall be under the supervision of the Secretary of
Public
Works and Communications, any provision of law to the contrary
notwithstanding.
(c) Subject to the
approval
of the Municipal Mayor, City Mayor, or Provincial Governor in the
proper
case, and other civil service laws and rules, the Building Official may
appoint such number of officers, inspectors, assistants, or other
employees
possessing the necessary qualifications and competency as may be
authorized
by the Municipal Council, City Council, or Provincial Board, as the
case
may be. He may deputize such technically qualified employees as may be
necessary to carry out the provisions of this Code. For purposes of
this
Subsection, the terms "necessary qualifications and competency" and
"technically
qualified" shall mean that the person to be deputized shall have passed
the highest grade of examination called for in the applicable law
regulating
the practice of the branch of engineering or architecture related to or
associated with the duties and powers which the person to be deputized
shall assume.
SECTION 1.02.03: Building
permits
(a) Any person, firm,
or
corporation, including any department, office, bureau, agency of
instrumentality
of the government intending to construct, alter, repair, move, convert
or demolish any building or structure, or cause the same to be done,
shall
obtain a building permit from the Building Official for whichever of
such
work is proposed to be undertaken for the building or structure, before
any such work is started.
(b) Appropriate rules
and
regulations shall be set by the Secretary concerning:
(1) Forms for application
for building permits;
(2) Procedures to be
observed
in securing such permits;
(3) Procedures to be
observed
in the issuance, suspension, and revocation of such building permits;
and
(4) Type, nature, and
scope
of plans and specifications, and other requisite documents, which shall
be prepared and designed by a licensed architect or engineer.
(c) When authorized by
the
Building Official in accordance with the provisions of this Code, plans
and specifications need not be submitted for the following:
(1) Group A traditional
indigenous type of dwelling construction costing not more than three
thousand
pesos (P3,000.00); and
(2) Group J Division 1
Occupancy
of Type 1 conventional wood frame construction or of the traditional
indigenous
type of construction costing not more than three thousand pesos
(P3,000.00).
(d) The applicant for a
building permit for private buildings or structures after having
complied
with all the requirements prescribed therefor in accordance with the
provisions
of this Code, shall be issued a building permit within fifteen (15)
days
from the date of payment of the permit fee for Groups A and J
Occupancies
and within thirty (30) days from the date of payment of the permit fee
for other Group Occupancies, unless the Building Official or his Deputy
authorized to issue the permit shall inform the applicant in writing
why
the permit should not be issued, and shall indicate thereon the
particular
provisions of the Code violated by the applicant or the particular
requirements
not complied with. Within fifteen (15) days from the date of receipt by
the applicant of advice from the Building Official or his Deputy
authorized
to issue the permit why the building permit should not be issued, or
why
the building permit is suspended or revoked, the applicant may appeal
the
non-issuance, suspension, or revocation thereof, to the Mayor of the
chartered
city or municipality, or the Governor of the province where the
building
or structure for which the permit is being applied for is located. Said
appeal shall be decided within fifteen (15) days from receipt thereof,
otherwise, the applicant may bring the matter to the proper Court of
Justice
for final disposition.
(e) All public
buildings
shall conform to the provisions of this Code and the Building Official
of the city or province where the public building is located shall
issue
the building permit therefor, stating in writing that such public
building
conforms to the requirements of the Code. For national public
buildings,
the Secretary of Public Works and Communications shall issue a
certification
that such a building conforms to the Code. Public buildings shall be
exempt
from payment of building permit, inspection, another fees.
SECTION 1.02.04: Fees
(a) Regulations on
building
permit, inspection and other fees, and for compliance with the same
shall
be covered by city and municipal ordinances: Provided, That Traditional
indigenous family dwellings under Section 1.01.04 (d) shall be exempt
from
payment of building permit fees.
SECTION 1.02.05: Inspection
ad Certificates of Occupancy
(a) Inspection. The
duly
licensed architect or engineer engaged by the owner to undertake
inspection
and detailed supervision of the construction shall periodically certify
that the construction conforms to the plans and specifications
submitted
in the application for a building permit. Upon submission of such
periodic
certifications during the progress of construction, the Building
Official
shall periodically issue the required authority to continue with the
subsequent
phases of construction, without prejudice to his right to conduct on
his
own initiative any inspection of the said construction. Upon completion
of the construction, the said duly licensed architect or engineer shall
submit to the Building Official the final certification that the
building
conforms to the provisions of the Code and with the detailed plans and
specifications submitted.
(b) Certificates of
Occupancy.
The proper Certificate of Occupancy shall be issued to the applicant
within
seven (7) days from completion of the requirements for inspection and
occupancy
and payment of any and all fees therefor, unless the building Official
or his Deputy issuing the Certificate shall show cause in writing why
the
Certificate should not be issued and shall indicate thereon the
particular
provisions of the Code violated or the particular requirements not
complied
with. Within fifteen (15) days from receipt by the applicant of the
advice
from Building Official or his Deputy authorized to issue the
certificate
why the certificate should not be issued, or why the certificate is
suspended
or revoked, the applicant may appeal the non-issuance, suspension, or
revocation
thereof, to the Mayor of the chartered city or municipality, or the
Governor
of the province where the building for which the certificate is being
applied
for is located. Said appeal shall be decided within fifteen (15) days
from
receipts thereof, otherwise, the applicant may bring the matter to the
proper Court of Justice for final disposition. The building may be
occupied
only upon issuance of the Certificate of Occupancy.
chan robles virtual law
library
SECTION 1.02.06: Violations
of This Code Covering Designs, Materials, Methods of Construction, and
Workmanship
(a) In all cases of
violation
of this Code covering design, materials, methods of construction, and
workmanship,
the Building Official shall observe the following procedure in ordering
the alteration to conform to this Code or demolition of the building or
portion thereof:
(1) Where the building is
in the process of construction, the construction of the portion or
portions
in violation of this Code shall be stopped until the same shall have
been
altered to conform to this Code, unless such partial violation will
impair
the stability and safety of the whole or part of the structure, in
which
case, the whole construction shall be stopped.
(2) Where a building or
portion thereof has been constructed, the following procedure shall be
observed:
(3) If the owner, after receipts
of the order of alteration or demolition fails to comply with such
order
within a period of one year, said construction shall be declared a
nuisance
and be abated in accordance with the provisions of Article 699 of the Civil
Code of the Philippines.
(b) This Code shall not
be construed to deprive any person the right to avail himself of any
and
all judicial proceedings or remedies available under existing laws.
(c) Nothing in this
Chapter
is intended to diminish the powers vested in the different Boards of
Examiners
of the various architectural and engineering professions as provided
for
in existence laws regulating the practice of architecture and
engineering,
nor to restrict the designing engineering or architect in the exercise
of his professional discretion within the basic minimum standards and
requirements
embodied in Section 1.01.02 of this Code.
TITLE 2
- FIRE AND
FIRE-RESISTIVE
STANDARDS
Chapter
2.01 -
REQUIREMENTS
FOR FIRE ZONES
SECTION 2.01.01:
General
(a) Fire Zones
Defined.
Fire zones are areas within which only certain types of building are
permitted
to be constructed based on their use, occupancy, type of construction,
and resistance to fire.
(b) Building
Located
in More Than One Fire Zone. If a building or structure is located
in
more than one fire zone and more than one-third of its total floor area
is in a more restricted fire zone, then the entire building shall
conform
to the requirements for the more restricted area.
(c) Moved Building.
Any building or structure moved within or into any fire zone shall be
made
to comply with all the requirements for buildings of that fire zone.
(d) Temporary
Buildings.
Temporary buildings or structures conforming to the requirements of
this Code, used for the protection of the public around and in
conjunction
with construction work may be erected in any of the fire zones: Provided,
that such work is allowed by special permit from the Building Official
and such is used only for a limited period of time.
(e) Center Lines of
Streets.
For the purpose of this Chapter, the center line of an adjoining street
or alley may be considered an adjacent property line. Distance shall be
measured at right angles to the street or alley.
SECTION 2.01.02. Designation
of Fire Zones
(a) The Secretary shall
classify each type of fire zone in accordance to use, occupancy, type
of
construction, and resistance to fire subject to the provisions of this
Code.
(b) Based on the
classification
of fire zones, City Counsels or Municipal Boards, by resolution, shall
divide cities and municipalities into fire zones. Such division shall
be
in accordance with the local physical and spatial framework plans or
the
recommendation of the local city or municipal development body.
Chapter
2.02 -
FIRE-RESISTIVE
REQUIREMENTS AND STANDARDS FOR FIRE PROTECTION
SECTION 2.02.01: Fire-Resistive
Requirements
(a) Exterior bearing
and
nonbearing walls of Types II and III constructions shall have one-hour
fire-resistive rating; while those of types IV and V shall have
four-hour
fire-resistive rating.
(b) Interior bearing
walls,
permanent partitions, floors, and roofs of Types II to IV constructions
shall have one-hour fire-resistive rating; while those of Type V shall
have three-hour fire-resistive rating for walls, one-hour
fire-resistive
rating for partitions, and two-hour fire-resistive rating for vertical
openings, floors, and roofs.
(c) Structural frames
of
Types II and III constructions shall have one-hour fire-resistive
rating;
those of Type IV shall have two-hour fire-resistive rating; and those
of
Type V shall have three-hour fire-resistive rating.
(d) Exterior doors and
windows
shall have three-fourths-hour fire-resistive rating for all types of
construction.
SECTION 2.02.02: Fire-Resistive
Standards
(a) General.
Materials
and systems of fire-resistive purposes shall be classified according to
their fire-resistive ratings as determined by internationally accepted
testing methods, subject to the provisions of this Section.
(b) One-Hour
Fire-Resistive
Time Period Rating
(1) The following walls
and partitions shall have a one-hour fire-resistive rating: Solid
masonry,
10 centimeters (4 inches) thick; hollow unit masonry, 15 centimeters (6
inches) thick; solid concrete, 10 centimeters (4 inches) thick; stud
walls
covered on each side with 1.9 centimeters (3/4 inch) lath and plaster,
1.6 centimeters (5/8 inch) of vermiculite gypsum board, or 2.5
centimeters
(1 inch) of gypsum board; and 5 centimeters (2 inches) nominal
thickness
tongue and groove wood, or two layers of 1.9 centimeters (3/4 inch)
tongue
and groove wood separated by sheet metal or asbestos paper and treated
on each side with a fire-retardant coating having a flame-spread rating
of 50 or less. Square-edged boards may be used is the layers are laid
at
right angles with each other.
(2) The following
floors
shall have a one-hour fire-resistive rating: masonry or concrete, 10
centimeters
(4 inches) thick; wood joists having two layers of flooring above and a
plaster or gypsum board ceiling, 1.9 centimeters (3/4 inch) in
thickness
- the two layers of flooring shall be separated by sheet metal or
asbestos
building paper; 6.3 centimeters (2-1/2 inches) net thickness tongue and
grooved wood floors covered with 1.9 centimeters (3/4 inch) wood
flooring
laid at right angles thereto. The supporting beams for such floors
shall
be not less than 15 centimeters (6 inches) in minimum dimension.
(3) The following
protections
for metal structural members shall have one-hour fire-resistive rating:
2.5 centimeters (1 inch) of concrete; 3.8 centimeters (1-1/2 inches) of
masonry; and metal lath and 2.5 centimeters (1 inch) of plaster.
(4) The following shall
also have a one-hour fire-resistive rating; wood colums, 20 centimeters
(8 inches) or more in least dimension; and wood beams, 15 centimeters
(6
inches) or more in least dimension.
(c) Two-Hour
Fire-Resistive
Time Period Rating
(1) The following
partitions,
walls, and floors shall have a two-hour fire-resistive rating: solid
masonry,
15 centimeters (6 inches) thick; hollow unit masonry, 20 centimeters (8
inches) thick; and solid concrete, 127 centimeters (5 inches) thick.
(2) The following
protections
for metal structural members shall have a two-hour fire-resistive
rating.
3.8 centimeters (1-1/2 inches) of concrete; 5 centimeters (2 inches) of
masonry; and two layers of metal lath and plaster with 1.9 centimeters
(3/4 inch) air space between and having a total thickness of 6.3
centimeters
(2-1/2 inches).
(d) Three-Hour
Fire-Resistive
Time Period Rating
(1) The following
partitions,
walls, and floors shall have a three-hour fire-resistive rating: solid
masonry, 17.8 centimeters (7 inches) thick; hollow unit masonry, 25.4
centimeters
(10 inches) thick; and solid concrete, 15 centimeters (6 inches) thick.
(2) The following
protection
for metal structural members shall have a three-hour fire resistive
rating:
centimeters (2 inches) of concrete; 7.6 centimeters (3 inches) of
masonry.
(e) Four-Hour
Fire-Resistive
Time Period Rating
(1) The following
partitions,
walls, and floors shall have a four-hour fire resistive rating: solic
masonry
walls, 20 centimeters (8 inches) thick; hollow unit masonry, 30
centimeters
(12 inches) thick; and solid concrete, 17.8 centimeters (7 inches)
thick.
(f) Steel Joists.
Steel joist floors shall have from one to four-hour fire-resistive
rating
based on internationally accepted standards of engineering.
(g) Flame-Proof
Materials.
Materials required to be flame-proofed shall be treated with a
flame-retardant
having flame-spread rating of 50 less as determined by the "Tunnel
Test".
SECTION 2.02.03: Interior
Wall and Ceiling Finish
(a) General.
Finishes
for interior walls and ceilings of any building shall be classified
according
to their flame-spread characteristics using the internationally
accepted
"Tunnel Test" or other equivalent test for fire protection. The class
of
materials according to flame-spread characteristics shall be determined
for each occupancy group. The smoke density shall not be greater than
that
obtain from the burning of untreated wood under similar conditions when
tested in accordance with the "Tunnel Test" in the way intended for
use.
The products of combustion shall be no more toxic than the burning of
untreated
wood under similar conditions.
(b) Interior Finish
Materials.
Interior walls and ceiling finish shall mean interior wainscoting,
paneling, or other finish applied structurally or for decoration,
acoustical
correction, surface insulation or similar purposes. Requirements for
finishes
shall not apply to trim, doors, and windows or their frames, nor to
materials
which are less than one millimeter (0.039 inch) in thickness cemented
to
an incombustible backing. Interior finish materials applied to walls
and
ceilings shall be tested as specified herein and regulated for purposes
of limiting flame-spread.
SECTION 2.02.04: Promulgation
of Fire-Resistive Regulations
(a) The Secretary shall
promulgate appropriate standards and regulations on the testing of
materials
for flame-spread characteristics; application of controlled interior
finish;
finishes based on occupancy; materials and tests on fire dampers, fire
tests of building construction and materials, fire tests of door
assemblies,
tin-clad fire doors, fire test of window assemblies, installation of
fire
door and fire windows, and smoke and fire detectors for fire protective
signaling systems; fire-resistive protection of structural members;
fire-resistive
walls and partitions; fire-resistive floor-ceilings or roof-ceilings;
fire-resistive
assemblies for protection of openings; and fire-retardant roof
coverings.
TITLE 3
-
REQUIREMENTS
BASED ON OCCUPANCY
Chapter
3.01 -
CLASSIFICATION
OF ALL BUILDINGS BY
USE OR
OCCUPANCY
AND
GENERAL REQUIREMENTS
FOR ALL
OCCUPANCIES
SECTION 3.01.01: Occupancy
Classified
(a) Building proposed,
for
construction shall be identified according to its use or the character
of its occupancy and shall be classified as follows:
(1) Group A - Residential:
Dwellings. Group A Occupancies shall include dwellings.
(2) Group B -
Residential:
Hotels and Apartments. - Group B Occupancies shall include boarding or
lodging houses, hotels, apartment houses, convents, and monasteries
(each
accomodating more than 10 persons).
chan robles virtual law
library
(3) Group C - Education
and Recreation. Group C Occupancies shall be any building used for
school
or day care purposes more than eight hours per week, involving
assemblage
for instruction, education, or recreation, and not classed in Group I
or
in Divisions 1 and 2 of Group H Occupancies.
(4) Group D -
Institutional.
Group D Occupancies shall include: Division 1 - Mental hospitals,
mental
sanitariums, jails, prisons, reformatories, and buildings where
personal
liberties of inmates are similarly restrained; Division 2 - Nurseries
for
full-time care of children under kindergarten age, hospitals,
sanitariums,
nursing homes with non-ambulatory patients, and similar buildings (each
accommodating more than five persons); Division 3 - Nursing homes for
ambulatory
patients, homes for children of kindergarten age or over (each
accommodating
more than five persons); Provided, That Group D Occupancies shall not
include
buildings used only for private residential purposes or for a family
group.
(5) Group E - Business
and
Mercantile. Group E Occupancies shall include: Division 1 - Gasoline
filling
and service stations; storage garage and boat storage structures where
no work is done except exchange of parts and maintenance requiring no
open
flame, welding, or the use of highly flammable liquids; Division 2 -
Wholesale
and retail stores, office buildings, drinking and dining establishments
having an occupant load test than 100, printing plants, municipal
police
and fire stations, factories and workshops using materials not highly
flammable
or combustible, storage and sales room for combustible goods, and paint
stores without bulk handling, and Division 3 -Aircraft hangars where no
repair work is done except exchange of parts and maintenance requiring
no open flame, welding, or the use of highly flammable liquids; open
parking
garages and heliports.
(6) Group F -
Industrial.
Group F Occupancies shall include: Ice plants, power plants, pumping
plants,
cold storage, and creameries; factories and workshops using
incombustible
and non-explosive materials; and storage and sales rooms of
incombustible
and non-explosive materials.
(7) Group G - Storage
and
Hazardous. Group G Occupancies shall include: Division 1 - Storage and
handling of hazardous and highly flammable or explosive materials other
than flammable liquids; Division 2 - Storage and handling of flammable
liquids; dry cleaning plants using flammable liquids; paint stores with
bulk handling; paint shops and spray painting rooms, and shops;
Division
3 - Wood working establishments, planning mills and box factories,
shops
factories where loose, combustible fibers or dust are manufactured,
processed
or generated; warehouses where highly combustible material is stored;
Division
4 - Repair garages; and Division 5 - Aircraft repair hangars.
(8) Group H - Assembly
Other
Than Group I. Group H Occupancies shall include: Division 1 - Any
assembly
building with a stage and an occupant load of less than 100 in the
building;
Division 2 - Any assembly building without a stage and having an
occupant
load of 300 or more in the building; Division 3 - Any assembly building
without a stage and having an occupant load of less than 300 in the
building,
including such buildings used for school purposes less than eight hours
per week; and Division 4 - Stadiums, reviewing stands, amusement park
structures
not included within Group I or Divisions 1, 2, and 3, Group H
Occupancies.
(9) Group I - Assembly
Occupant
Load 1000 or More. Group I Occupancies shall be any assembly building
with
a stage and an occupant load of 1000 or more in the building.
(10) Group J -
Accessory.
Group J Occupancies shall include: Division 1 - Private garages,
carports,
sheds, and agricultural buildings; Division 2 - Fences over 1.80 meters
(6 feet) high, tanks, and towers.
(b) Other subgroupings
or
divisions within Groups A to J may be determined by the Secretary. Any
other occupancy not mentioned specifically in this Section, or about
which
there is any question, shall be included in the Group which its use
most
nearly resembles based on the existing or proposed life and fire hazard.
(c) The Building
Officials
shall identify and indicate in the Certificate of Occupancy the
appropriate
classification to which a building or structure to be constructed
belongs.
SECTION 3.01.02: Change
in Use
(a) No change shall be
made
in the character of occupancies or use of any building which would
place
the building in a different division of the same group of occupancy or
in a different group of occupancies, unless such buildings is made to
comply
with the requirements for such division or group of occupancy: Except,
That the character of occupancy of existing buildings may be changed
subject
to the approval of the Building Official and the building may be
occupied
for purposes set forth in other Groups without conforming to all the
requirements
for those Groups, provided the new or proposed use is less hazardous,
based
on life and fire risk, than the existing use.
SECTION 3.01.03: Mixed
Occupancy
(a) General.
When
a building is used for more than one occupancy purposes, each part of
the
building comprising a distinct "Occupancy" shall be separated from any
other occupancy. When a building is used for more than one occupancy
purpose,
it shall be subject to the most restrictive requirements for the
occupancies
concerned: Except, - (1) When a one-story building houses more than one
occupancy, each portion of the building shall conform to the
requirements
for the occupancy housed therein, and the area of the building shall be
such that the sum of the actual areas divided by the allowable area for
each separate occupancy shall not exceed one; and (2) Where minor
accessory
uses do not occupy more than 10 per cent of the area of any floor of a
building, nor more than 10 per cent of the basis are permitted in the
occupancy
requirements. The major use of the building shall determine the
occupancy
classification provided the uses are separated in accordance with
requirements
for occupancy separation.
(b) Forms of
Occupancy
Separation. Occupancy separations shall be vertical or horizontal
or
both, or when necessary, of such other form as may be required to
afford
a complete separation between the various occupancy divisions in the
building.
(c) Types of
Occupancy
Separation. Occupancy separations shall be classed as "One-Hour
Fire-Resistive"
"Two-Hour Fire-Resistive", "Three-Hour Fire-Resistive", and "Four-Hour
Fire-Resistive".
(1) A "One-Hour
Fire-Resistive
Occupancy Separations" shall be of not less than one-hour
fire-resistive
construction. All openings in such a separations shall be protected a
fire
assembly having a one-hour fire-resistive rating.
(2) A "Two-Hour
Fire-Resistive
Occupancy Separation" shall be of not less than two-hour fire-resistive
construction. All openings in such separation shall be protected by a
fire
assembly having a one and one-half-hour fire-resistive rating.
(3) A "Three-Hour
Fire-Resistive
Occupancy Separation" shall be of not less than three-hour
fire-resistive
construction. All openings in walls forming such separation shall be
protected
by a fire assembly having a three-hour fire-resistive rating. The total
width of all openings in any three-hour fire-resistive occupancy
separation
wall in any one-story shall not exceed 25 per cent of the length of the
wall in that story and no single opening shall have an area greater
than
10.00 square meters (107.1 square feet). All openings in floors forming
a "Three-Hour Fire-Resistive Occupancy Separation" shall be protected
by
vertical enclosures extending above and below such openings. The walls
of such vertical enclosures shall be of not less than ten-hours
fire-resistive
construction, and all openings therein shall be protected by a fire
assembly
having one and one-half-hour fire-resistive rating.
(4) A "Four-Hour
Fire-Resistive
Occupancy Separation" shall have no openings therein and shall be of
not
less than four-hour fire-resistive construction.
(d) Fire Ratings
for
Occupancy Separation. Occupancy separations shall be provided
between
various groups, subgroupings, or divisions of occupancies. The
Secretary
shall promulgate rules and regulations for appropriate occupancy
separations
in buildings of mixed occupancy: Provided, That where any
occupancy
separation is required, the minimum shall be a "One-Hour Fire-Resistive
Occupancy Separation"; and where the occupancy separation is
horizontal,
structural members supporting the separation shall be protected by
equivalent
fire-resistive construction.
SECTION 3.01.04: Location
on Property
(a) General. Buildings
shall
adjoin or have access to a public space, yard, or street on not less
than
one side. Required yards shall be permanently maintained. For the
purpose
of this Section, the center line of an adjoining street or alley shall
be considered an adjacent property line. Eaves over required windows
shall
be not less than 75 centimeters (30 inches) from the side and rear and
rear property lines.
(b) Fire Resistance
of
Walls. Exterior walls shall have fire resistance and opening
protection
in accordance with requirements set by the Secretary. Projections
beyond
the exterior wall shall not extend beyond a point one-third the
distance
to the property line from an exterior wall; or a point one-third the
distance
from an assumed vertical plane located where fire-resistive protection
of openings is first required due to location on property, whichever is
the least restrictive. Distance shall be measured at right angles from
the property line. When openings in exterior walls are required to be
protected
due to distance from property line, the sum of the area of such
openings
shall not exceed 50 per cent of the total area of the wall in each
story.
(c) Buildings on
Same
Property and Buildings Containing Courts. For the purpose of
determining
the required wall and opening protection, buildings on the same
property
and court walls shall be assumed to have a property line between them.
When a new building is to be erected on the same property with an
existing
building, the assumed property line from the existing building shall be
the distance to the property line for each occupancy as set forth by
the
Secretary: Provided, That two or more buildings on the same property
may
be considered as portions of one building of the aggregate area of such
buildings is within the limits of allowable floor areas for a single
building;
and that when the buildings so considered house different occupancies
or
are of different types of construction, the area shall be that allowed
for the most restricted occupancy or construction.
SECTION 3.01.05: Allowable
Floor Areas
(a) Areas of One-Story
Buildings
and Building Over One Story. Allowable floor areas for one-story
buildings
and buildings over one story shall not exceed the limits determined in
accordance with occupancy groups and types of construction.
(b) Area Separation
Walls.
Each portion of a building separated by one or more area separation
walls
may be considered a separate building provided the area separation wall
meet the requirements of this Code.
SECTION 3.01.06: Allowable
Area Increases
(a) The floor area
hereinabove
provided may be increased in certain specific instances and under
appropriate
conditions, based on the existence of public space, streets, or yards
extending
along the adjoining two or more sides of the building or structure.
SECTION 3.01.07: Maximum
Height of Buildings and Increases
(a) The maximum height
and
number of stories of every building shall be dependent upon the
character
of the occupancy and the type of construction, and shall not exceed the
limits determined by population density, building bulk, widths of
streets,
and car parking requirements. The height shall be measured from the
highest
adjoining sidewalk or ground surface, provided that the height measured
from the lowest adjoining surface shall not exceed such maximum height
by more than 3.00 meters (10 feet): Except, That towers, spires, and
steeples,
erected as a part of a building and not used for habitation or storage,
are limited as to height only by structural design if completely of
incombustible
materials, or may extend not to exceed 6.00 meters (19 feet, 8 inches)
above the height limits for each occupancy group if of combustible
materials.
SECTION 3.01.08: Maximum
Requirements for Group A Dwellings: One Two Stories
(a) Dwelling
Location
and Lot Occupancy. The dwelling shall occupy not more than 90 per
cent
of a corner lot and 80 per cent of an inside lot, and subject to the
provisions
on easements of light and view of the Civil Code of the Philippines,
shall
be at least 2.00 meters (6 feet, inches) from the property line.
(b) Light and
Ventilation.
Every dwelling shall be so constructed and arranged as to provide
adequate
light and ventilation.
(1) Habitable rooms,
bathrooms,
toilet rooms and utility rooms shall have a height of not less than
2.40
meters (8 feet), measured from floor to ceiling.
(2) Rooms shall have a
minimum
size of 6.00 square meters (65 square feet) with a least horizontal
dimension
of 2.00 meters (6 feet, 7 inches) for rooms of human habitations; 3.00
square meters (32 feet) with a least horizontal dimension of 1.50
meters
(5 feet) for kitchens; and 1.20 square meters (13 square feet) with a
least
horizontal dimension of 90 centimeters (3 feet) for bathrooms.
(3) Windows shall be at
least 1/10th of the floor area of the room.
(c) Sanitation. Every
dwelling shall be provided with at least one sanitary toilet and
adequate
washing and drainage facilities.
(d) Foundation.
Footing
shall be of sufficient size and strength to support the load and
dwelling
and shall be at least 30 centimeters (1 foot) thick and 60 centimeters
(2 feet) below the surface of the ground. Each post shall be anchored
to
such footings by straps and bolts of adequate size.
(e) Post or
Suportales.
The dimensions of wooden post or suportales shall be those found in
Table
3.01 - A Dimension of Wooden Posts or Suportales (Annex B).
(f) Floor. The
live
load of the first floor shall be at least 200 kilograms per square
meter
(40 pounds per square foot) and for the second floor, at least 150
kilograms
per square meter (30 pounds per square foot).
(g) Roof. The
wind
load for roofs shall be at least 150 kilograms per square meter (30
pounds
per square foot).
(h) Stairs.
Stairs
may be 75 centimeters (30 inches) wide, with a rise of 20 centimeters
(8
inches) and a run of 23 centimeters (9 inches).
(i) Entrance and
Exit.
There shall be one entrance and one exit.
(j) Electrical
Outlets.
There shall be at least one convenience outlet per 6.00 meters (20
feet) of wall measured along the floor and one light outlet for every
room.
(k) Mechanical
Requirements.
Family dwellings not more than two stories shall be exempt from the
requirements of the Mechanical Code.
SECTION 3.01.09: Requirements
for Group Occupancies
(a) Subject to the
provisions
of this Code, the Secretary shall promulgate regulations for each
occupancy
group covering: allowable construction, height, and area; location on
property,
exit facilities, light, ventilation, and sanitation; enclosure of
vertical
openings; fire-extinguishing system; and special hazards.
TITLE 4
- TYPES OF
CONSTRUCTION
Chapter
4.01 -
CLASSIFICATION
OF ALL BUILDINGS BY TYPES OF CONSTRUCTION AND GENERAL REQUIREMENTS
SECTION 4.01.01:
Types
of
Construction
(a) The requirements of
this Chapter are minimum for the varying degrees of public safety and
resistance
to fire. Every building proposed for construction shall be identified
according
to the following:
(1) Type I. Type I
Buildings
shall be of wood construction. The structural elements may be any of
the
materials permitted by this Code.
(2) Type II. Type II
Buildings
shall be of wood construction with protective fire-resistant materials
and one-hour fire-resistive throughout: Except, That permanent
nonbearing
partitions may use fire-retardant treated wood within the framing
assembly.
(3) Type III. Type III
Buildings
shall be masonry and wood construction, Structual elements may be any
of
the materials permitted by this Code: Provided, That the building shall
be one-hour fire-resistive throughout. Exterior walls shall be of
incombustible
fire-resistive construction.
(4) Type IV. Type IV
Building
shall be of steel, iron, concrete, or masonry construction. Walls and
permanent
partitions shall be of incombustible fire-resistive construction:
Except,
That permanent nonbearing partitions of one-hour fire resistive
construction
framing assembly.
(5) Type V. Type V
Buildings
shall be fire-resistive. The structural elements shall be of steel,
iron,
concrete, or masonry construction. Walls and permanent partitions shall
be incombustible fire-resistive construction.
(b) Other subtypes or
divisions
within Types I to V may be determined by the Secretary. Any building
which
does not conform entirely to a type of construction herein set forth
shall
be classified into a type having an equal or lesser degree of
fire-resistance
of the building.
(c) The Building
Official
shall identify and indicate in the Certificate of Occupancy the
appropriate
classification to which a building or structure to be constructed
belongs.
SECTION 4.01.02: Change
in Type
(a) No change shall be
made
in the type of construction of any building which would place the
building
in a different subtype or type of construction unless such bidding is
made
to comply with the requirements for such subtype or type of
construction:
Except, That the type of construction of existing buildings may be
changed
subject to the approval of the Building Official and the building may
be
constructed for purposes set forth in other Types without conforming to
all the requirements for those Types, provided the new or proposed
construction
is less hazardous, based on life and fire risk, than the existing
construction.
SECTION 4.01.03: Requirements
on Types of Construction
(a) Subject to the
provisions
of this Chapter, the Secretary shall promulgate regulations for each
type
of construction, and promulgate rules and regulations therefor,
covering:
structural framework, exterior walls and openings, interior walls and
enclosures,
floors, exits and stars construction, and roofs.
TITLE -
LIGHT,
VENTILATION,
AND SANITATION
Chapter
5.01 -
LIGHT
AND VENTILATION
SECTION 5.01.01:
General
(a) Subject to the
provisions
of the Civil
Code on easement on light and view, and to provisions of this
Title,
every building shall be so constructed, arranged, and equipped as to
provide
adequate light and ventilation.
(b) All building
erected
shall face a street or public alley or private street which has been
officially
approved.
(c) No building shall
be
altered nor arranged so as to reduce the size of any room or the
relative
area of windows to less than that provided for buildings under this
Code,
or so as to create an additional room, unless such additional room
conforms
to the requirements of this Code.
(d) No building shall
be
enlarged, so that the dimensions of any required court yard would be
less
than that prescribed for any such building.
SECTION 5.01.02: Measurement
of Site Occupancy
(a) The measurement of
site
occupancy or lot occupancy shall be taken at the ground level and shall
be exclusive of courts, yards, and light wells.
(b) Courtyards and
light
wells shall be measured clear of any projections from the walls
enclosing
such wells or yards with the exception of roof leaders, wall copings,
sills,
or steel fire escapes, not exceeding 1.20 meters (4 feet) in width.
SECTION 5.01.03: Percentage
of Site Occupancy
(a) The maximum site
occupancy
shall be governed by the use, type of construction, and height of the
building,
and the use, area, nature and location of the site, subject to the
provisions
of local zoning requirements and in accordance with rules and
regulations
set forth by the Secretary.
SECTION 5.01.04: Minimum
Size of Courts and Their Least Dimensions
(a) The minimum size of
courts and their least dimensions shall be dependent upon the use, type
of construction, and height of the building subject to the requirements
set forth by the Secretary: Provided, That in no case shall be
the
minimum horizontal dimension of courts be less than 2.00 meters (6
feet,
7 inches).
(b) All inner courts
shall
be connected to a street or yard, either by a passageway with a minimum
width of 1.20 meters (4 feet) or by a door through a room or rooms.
SECTION 5.01.05: Ceiling
Heights
(a) Habitable rooms,
bathrooms,
toilet rooms, storage rooms, and utility rooms shall have a ceiling
height
of not less than 2.40 meters (8 feet), measured from the floor to the
ceiling:
Provided, That for buildings of more than one story, the minimum
ceiling height of the first story shall be 2.70 meters (9 feet) and
2.40
meters (8 feet) for the second story, and succeeding stories. Garages
shall
have an unobstructed headroom clearance of not less than 2.10 meters (7
feet) above the finished floor.
SECTION 5.01.06: Minimum
Size of Rooms and Their Least Dimensions
(a) The minimum sizes
of
rooms and their least horizontal dimensions shall be as follows: 6:00
square
(65 square feet) with at least nominal dimension of 2.00 meters (6 feet
7 inches) for rooms for human habitation; 3.00 square meters (32 square
feet) with a least horizontal dimension of 1.50 meters (5 feet) for
kitchens;
and 1.20 square meters (12 square feet) with a least horizontal
dimension
of 0.90 meter (3 feet) for bathrooms.
SECTION 5.01.07: Minimum
Air Space Requirements in Determining the Size of Rooms
(a) The following
minimum
air spaces shall be provided:
(1) For school rooms: 3.00
meters (106 cubic feet) with 1.00 square meter (10.7 square feet) of
floor
area per person.
(2) For workshops,
factories,
and offices: 10.00 cubic meters (354 cubic feet) or air space per
person
at daytime and 14.00 cubic meters (494 cubic feet) of air space per
person
at night time.
(3) For habitable
rooms:
14.00 cubic meters (494 cubic feet) of air space per adult person and
7.00
cubic meters (247 cubic feet) of air space per child under 10 years of
age.
SECTION 5.01.08: Window
Openings
(a) Every room intended
for any use, not otherwise provided with air-conditioning or mechanical
ventilation system as herein provided in this Code, shall be provided
with
a window or windows whose total area of openings shall be at least
1/10th
the floor area of the room, and such shall open directly to a court,
yard,
public way or alley, or water course.
SECTION 5.01.09: Mezzanine
Floor
(a) A Mezzanine floor
is
a partial, intermediate floor in any story or room of a building having
an area not more than one-half of the area of the room or space in
which
it is constructed.
(b) A mezzanine floor
shall
be constructed with a clear ceiling height of not less than 1.90 meters
(6 feet, 4 inches) above and below.
SECTION 5.01.10: Vent
Shafts
(a) Size. Vent
shafts
shall have a cross-sectional area of not less than 1/10th of a square
meter
for every meter of height of shafts (1 square foot per 10 feet) but not
less than 1.00 square meter (10.7 square feet) in any case. No such
shaft
shall be less than 60 centimeters (2 feet) in its least dimension.
(b) Skylights.
Unless
open to the outer air at the top for its full area, such shaft shall be
covered by a skylight having a net area of fixed louver openings equal
to the maximum required shaft area.
(c) Air Ducts.
Air
ducts shall be connected to a street or court by a horizontal duct or
intake
at a point below the lowest window opening on such shaft. Such duct or
intake shall have a minimum unobstructed cross-sectional area of not
less
than 0.30 square meter (3.2 square feet) with a minimum dimension of 30
centimeters (1 foot). The opening to the duct or intake shall not be
less
than 30 centimeters (1 foot) above the bottom of the shaft and the
street
surface or bathroom of court, at the respective ends of the conduct or
intake.
SECTION 5.01.11: Ventilating
Skylights
(a) Skylights.
Skylights
shall have a glass area not less than that required for the window they
replace. They shall be equipped with movable sashes or louvers of an
aggregate
net area not less than that required for openable parts in the window
they
replace or with approved ventilation of equal efficiency.
(b) Ventilation.
Rooms containing industrial heating equipment shall be provided with
adequate
artificial means of ventilation to prevent excessive accumulation of
hot
or polluted air.
chan robles virtual law
library
SECTION 5.01.12:
Artificial
Ventilation
(a) General. When
artificial ventilation is required, the equipment shall be designed and
constructed to meet the following requirements in air changes:
(1) Business and
Workrooms